BNBC 2006 · Part 8 — Building Services

Chapter 1 — Lighting

Superseded by BNBC 2020 (in force from 11 February 2021) — see note.

Sections in this chapter

Lighting

1.1        Scope

 The basic requirements for building lighting are that adequate light of the right quality is provided and that proper attention is given to the appearance and artistic features of the lighting fixtures and the effects they produce. This chapter, read together with Chapter 2 Electrical Installation covers the illumination level requirements in buildings and methods for achieving these requirements.

1.2        Terminology

 This section provides an alphabetical list of the terms used in and applicable to this chapter of the Code. In case of any conflict or contradiction between a definition given in this section and that in Part 1, the meaning provided in this section shall govern for interpretation of the provisions of this chapter.

        Brightness : The luminous intensity of any surface in a given direction per unit of projected area of the surface, as viewed from that direction.

 COLOUR :  Aspect of visual perception by which an observer may distinguish between two fields of view of the same size, shape and structure, as may be caused by differences in the spectral composition of the radiation concerned.

        Colour  Appearance :  One of the two factors characterizing the colour qualities of a lamp. Lamps are usually divided into three groups according to their colour appearance : warm, intermediate and cool.

        Colour Rendering  :  The colour rendering property of a lamp is described by its colour rendering index, Ra; the higher the index the better the colour rendering property. The colour rendering index of a lamp is a measure of the degree to which the psychophysical colours of objects illuminated by the lamp conform to those of the same objects illuminated by a reference lamp, under specified conditions.

        Contrast :  The contrast of a small object of uniform luminance seen against a background of uniform luminance is the difference between object luminance and background luminance expressed as a ratio of the background luminance.

 GLARE :  The sensation produced by luminance within the visual field that is sufficiently greater than the luminance to which the eyes are adapted to cause annoyance, discomfort, or loss in visual performance and visibility. The magnitude of the sensation of glare depends upon such factors as the size, position and luminance of a source, the number of sources and the luminance to which the eyes are adapted.

        Glare, Direct : Glare caused by a bright light source appearing in the normal field of view of an observer.

        Glare, Disability : Glare that impairs the vision, measured in terms of deterioration of visual performance (contrast sensitivity).

        Glare, Discomfort :  Glare that induces a feeling of discomfort; the degree of discomfort can only be measured subjectively.

        Glare, Reflected :  Glare caused by the reflection of bright light source on a glossy surface.

        Illuminance :  The quantity of light or luminous flux falling on unit area of a surface.

        Illumination  :  The application of visible radiation to an object.

        Incandescence :  Emission of visible radiation by thermal excitation.

        Lamp, Fluorescent :  Discharge lamp in which most of the light is emitted by a layer of fluorescent material excited by the ultraviolet radiation from the discharge.

        Lamp, Incandescent : Lamp in which light is produced by means of an element heated to incandescence by the passage of an electric current.

        Lighting, General : Lighting designed to illuminate an area in general, without particular provision for any special local requirements within that area.

        Lighting, Localized : Lighting designed to increase the illuminance at certain specified positions; for instance those at which work is carried on.

        Lumen : The luminous flux emitted within unit solid angle (one steradian) by a point source having a uniform intensity of one Candela.

        Luminaire : A complete lighting apparatus consisting of a lamp or lamps together with the parts designed to distribute, filter or transform the light, to fix and protect the lamps and to connect them to the supply circuit.

        Luminance (at a point) :  The ratio of the luminous intensity in a given direction of an infinitesimal element of the surface containing the point under consideration to the orthogonally projected area of the element on a plane perpendicular to the given direction.  It is proportional  to the product of the illuminance and the surface reflectance, the latter being the ratio of the reflected luminous flux to the incident luminous flux.

        Luminous Flux :  The quantity characteristic of radiant flux which expresses its capacity to produce visual sensation evaluated according to the values of relative luminous efficiency for the light-adapted eye.

        MAINTENANCE FACTOR:  The ratio of the average illuminance on the working plane, after a certain period of use of a lighting installation, to the average illuminance obtained under the same conditions for the same lighting installation when new.

        Reflection FACTOR:   The ratio of light reflected from a surface to the total light falling on the surface. The reflection factor varies with the roughness of the surface as well as the darkness of the colour.

        Utilization FACTOR:  The ratio of the flux received on the working plane to the sum of the fluxes from all the lamps in the interior.

        Working Plane : A horizontal plane at a level at which work will normally be done. Where a visual task is required to be carried out throughout an interior, general illumination of the value recommended for the working plane is necessary; where the precise height and location of the task are not known or cannot be easily specified, the recommended value is that on a horizontal plane 850 mm above the floor level. For an industrial task, working plane for the purpose of general illumination levels may be taken at 760 mm above the floor level. For certain purposes, such as viewing the objects of art, the illumination levels recommended are for the vertical plane at which the art pieces are placed.

1.3 ILLUMINATION

1.3.1        Principle of Lighting

 The essential features of an efficient lighting system are :

- visual comfort through adequate illumination of the working surface, prevention of glare, and avoidance of shadows,  

- ease of maintenance.

 The design of a lighting system shall  involve :

a) careful planning of the brightness and colour pattern within both the working areas and the surroundings so that attention is drawn naturally to the important areas, detail is seen quickly and accurately, and the room is free from any sense of gloom or monotony,

b) use of directional lighting to assist perception of task detail,

c) controlling direct and reflected glare from light sources to eliminate visual discomfort,

d) minimizing flicker from certain types of lamps and paying attention to the colour rendering properties of the light,

e) the correlation of lighting throughout the building to prevent excessive differences between adjacent areas, so as to reduce the risk of accidents, and

f) the installation of emergency lighting systems, where necessary.

 Table 8.1.1  shows the general impressions associated with different illuminance and colour appearances of light. Table 8.1.2 gives the various colour rendering groups with examples of use.

Table 8.1.1

General Impressions Associated with Different Illuminance and Colour Appearances

Illuminance

 Associated Impression

(lux)

(Colour Appearance)

Warm

Intermediate

Cool

≤ 500

500 – 1000

1000 – 2000

2000 – 3000

≥  3000

pleasant

pleasant to stimulating

stimulating

stimulating to unnatural

unnatural

neutral

neutral  to pleasant

pleasant

pleasant  to stimulating

stimulating

cool

cool  to neutral

neutral

neutral to pleasant

pleasant

        Table 8.1.2

Lamp Colour Rendering Groups

Colour

rendering Group

Range of

Index Ra

Colour

Appearance

Examples of Use

Cool

Textile industries, paint and printing industries

1

Ra ≥ 85

Intermediate

Shops, hospitals

Warm

Homes, hotels, restaurants

2

 70 ≤  Ra < 85

Intermediate

Offices, schools, department store, fine industrial work

3

40 ≤  Ra < 70

Interiors where colour rendering is of comparatively minor importance

Note :        Certain applications, e.g. colour matching, may be extremely critical with regard to the colour rendering properties of the lamps used. Here, the minimum colour rendering index used shall be 90.

1.3.2         Planning the Brightness Pattern

 The brightness pattern seen within an interior is composed of three parts - brightness of the task itself, brightness of the immediate background of the task and brightness of the general surroundings of walls, ceiling, floor, equipment, furnishing etc.

        1.3.2.1        The illumination of all work areas within a building shall be a minimum of 150 lux.

        1.3.2.2          Where work takes place over the whole utilizable area of a room, the general illumination over that area shall  be reasonably uniform and the diversity ratio of minimum to maximum illumination shall not be less than 0.7. This diversity ratio does not however take into account the effects of any local lighting provided for specific tasks.

        1.3.2.3          When the task brightness appropriate to an occupation has been determined, the brightness of the other parts of the room shall be planned to give proper emphasis to visual comfort and interest. The recommended brightness ratios is shown in Table 8.1.3.

1.3.3        Lighting Calculations

        1.3.3.1          In order to determine the necessary number of lamps and luminaires for a specified illumination level or the average illuminance obtained from a particular lighting design, the Lumen Method of calculation shall be employed.

        1.3.3.2        Unless the reflection factors are known to the lighting designer, the triplet 0.7/0.5/0.3 for the reflectances of ceiling, walls and working plane respectively shall be used for offices and the triplet 0.7/0.5/0.1 for other premises. Typical reflection factors of smooth coloured surfaces are given in Table 8.1.4.

Table 8.1.3

Brightness Ratios Between Task, Adjacent Sources and Surroundings

For high task brightness  (above 100 cd/m2) :

Maximum ratio between task brightness and the adjacent sources like table tops

3 to 1

Maximum ratio between task brightness and illumination of the remote areas of the room not being used as work  areas

10 to 1

For low and medium task brightness (below 100 cd/m2)  

The task must be brighter than both the background and the surroundings; the lower the task brightness, the less critical is the relationship.

Table 8.1.4

Reflection Factors of  Smooth Coloured Surfaces

Colour

Reflection Factor

Colour

Reflection Factor

Flat white

Ivory

Buff

Yellow

Light tan

0.75 – 0.85

0.70 – 0.75

0.60 – 0.70

0.55 – 0.65

0.45 – 0.55

Light green

Grey

Blue

Red

Dark brown

0.40 – 0.50

0.30 – 0.50

0.25 – 0.35

0.15 – 0.20

0.10 – 0.15

1.3.4        Recommended Illumination Values

 The recommended values of illumination required for  buildings of different Occupancies, based on activity, are given in Tables 8.1.5 through 8.1.11. The initial illuminance should be higher than the recommended value to allow for the fact that the illuminance will inevitably drop below this value by the end of  the cleaning and relamping period. A gradual transition of brightness from one portion to another within the field of vision is recommended so as to avoid or minimize glare discomfort.

1.3.5        Artificial Lighting to Supplement Daylight

Supplementary lighting shall be used when illumination by daylight falls below 150 lux on the working plane.

 For providing supplementary artificial lighting when daylight availability becomes insufficient, cool daylight fluorescent tubes with semi-direct luminaires are recommended. To ensure a good distribution of illumination, the mounting height should be between 1.5 and 2.0 m above the work plane for a separation of 2.0 to 3.0 m between the luminaires.

1.4 LIGHT FITTINGS

 An electric lamp and its fitting, globe reflector etc., shall be regarded as one unit; they shall  be designed to suit each other and to give the desired distribution of light. Any focussing fittings used which enable the light distribution to be varied by adjustment of the lamp position shall also be designed for the type and size of lamp to be used.

1.4.1        Classification of Lamp Fittings

 Lamp fittings shall be classified into five categories according to the proportion of the total light output in the lower hemisphere. These are: direct fittings, giving 90-100 per cent light downwards; semi-direct fittings, giving  60-90 per cent downwards; general diffusing fittings, giving 40-60 per cent light downwards; semi-indirect fittings, giving 10-40 per cent light downwards; indirect fittings, giving 0-10 per cent light downwards.

Table 8.1.5  

Recommended Values of Illumination for Residential Buildings

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(lx)

Dwelling houses

 Bedrooms

General

Bed-head, Dressing table

Kitchens

Dining rooms (tables)

Bathrooms

General

Shaving, make-up

Stairs

Lounges

Garages and porches

Sewing and darning

Reading (casual )

Home work and sustained reading

Hotels

Entrance halls

Reception and accounts

Dining rooms (tables)

Lounges

Bedrooms

General

Dressing tables, bed heads, etc.

Writing rooms (tables)

Corridors

Stairs

Laundries

Kitchens

Food stores

Working areas

Goods and passenger lifts

Cloak-rooms and toilets

Bathrooms

Above mirror in bathrooms

50

150

200

100

100

300

100

100

70

600

150

300

150

300

100

150

100

150

300

70

100

200

100

250

70

100

100

300

Table 8.1.6

Recommended Values of Illumination for Educational Buildings

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance  (lx)

School and College   Assembly halls

General

When used for examinations

Platforms

Class and Lecture Rooms

Desks

Black boards

Embroidery and sewing rooms

Laboratories

Art  rooms

Offices

Staff rooms and common rooms

Corridors

Stairs

Gymnasia

General

Matches

Library

Living quarters

150

300

300

300

250

500

300

400

300

150

70

100

150

300

see Table 8.1.8

see Table 8.1.5

Table 8.1.7

Recommended Values of Illumination for Health Care Buildings

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance  (lx)

Hospitals and Clinics

Reception and waiting rooms

Out patient department

Wards

 General

Beds

Operating theatres

General

Tables (with adjustable operation lamp lighting)

Minor

Major

Doctor's examination rooms

Radiology departments

Casualty

Stairs and corridors

Dispensaries

150

150

100

150

300

2000

5000

150

100

150

100

250

Table 8.1.8

Recommended Values of Illumination for Assembly Buildings

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance  (lx)

Cinemas

 Foyers

 Auditorium

 Corridors

 Stairs

Libraries

Shelves (stacks)

Reading rooms (newspapers and magazines)

Reading tables

Book repair and binding

Cataloguing, sorting and stock rooms  

Museums and Art Galleries

Museums      

General

Displays

Art galleries

General

Paintings

Restaurant

Dining rooms

Cash desks

Self-carrying counters

Kitchens

Cloak-rooms and toilets

Theatres

Foyers

Auditorium

Corridors

Stairs

Sports Centre

Halls

Swimming pools

Lawn or table tennis, badminton, volley ball

Tournament

Club

Recreational

Shooting ranges

On target

Firing point

Range

Football

150

50

70

100

100

200

300

300

150

150

special lighting

100

200

100

300

300

200

100

150

70

70

100

150

150

300

200

100

 300

200

50

500

        Table 8.1.9

Recommended Values of Illumination for Business and Mercantile Buildings

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

 (lx)

Airport Building

Reception areas (desks)

Baggage, customs and immigration halls

Circulation areas, lounges

Banks

Counter, typing and accounting book areas

Public areas, lobby

Offices

Book binding

Pasting, punching and stitching

Binding and folding and miscellaneous machines

Finishing, blocking and inlaying

Dental Surgeries

Waiting rooms

Surgeries

General

Chairs

Laboratories

Doctor's Surgeries

Waiting rooms and consulting rooms

Corridors

Stairs

Eyesight testing (acuity) wall charts

         and near vision types

Jewellery and watch-making

Fine processes

Minute processes

Gem cutting, polishing and setting

Laundries and dry-cleaning works

Receiving, sorting, washing, drying, ironing

         (calendering) and despatch

Dry-cleaning and bulk machine work

Fine hand ironing, pressing, inspection,

          mending and spotting

Offices

Entrance lobby and reception areas

Conference rooms and executive offices

General offices

Business machine operation

Drawing office

General

Boards and tracing

Corridors and lift cars

Stairs

Lift landings

Telephone exchanges

Manual exchange rooms (on desk)

Main distribution frame room  

Shops and Stores

General areas

Stock rooms

Display windows

300

300

150

300

150

200

200

300

300

150

300

special lighting

300

150

70

100

450

700

3000

1500

200

200

300

150

300

300

450

300

450

70

100

150

200

150

150 to 300

200

500

Table 8.1.10

Recommended Values of Illumination for Industrial Buildings and Processes

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(lx)

Aircraft Factories and Maintenance Hangars

Stock parts productions

450

Drilling, riveting, screw fastening, sheet aluminium layout and template work, wing sections, cowing, welding, sub-assembly, final assembly and inspection

300

Maintenance and repair (hangars)

300

Assembly Shops

Rough work, for example frame assembly and assembly of heavy   machinery

150

Medium work, for example machined parts, engine assembly

300

Fine work, for example  radio and telephone   equipment, typewriter

 and office machinery  assembly

700

Very fine work, for example  assembly of very small precision

         mechanisms and instruments

1500

Automobile Manufacturing

Frame assembly

Chassis assembly line

 Final assembly and inspection line

Body manufacturing

200

300

600

Parts

Assembly

Finishing and inspection

200

300

700

Automobile Service Garages

Repairs

Active traffic areas

Storage

250

100

25

Bakeries

General working area

Decorating and icing

150

250

Breweries and Distilleries

General working areas

Brewhouse, bottling and canning plants

Bottle inspection

150

200

special lighting

Carpet Factories

Winding and beaming

Designing, Jacquard card cutting, setting pattern, tufting, topping, cutting,

        hemming and fringing

Weaving, mending and inspection

200

300

450

Chemical Works

Hand furnaces, boiling tanks, stationary driers, stationary and gravity    

      crystallizers

Mechanical furnaces, evaporators, filtration, mechanical crystallizers, bleaching

 Tanks for cooking, extractors, percolators

150

200

200

Chocolate and Confectionery Factories

Mixing, blending and boiling

Chocolate husking, winnowing, fat extraction, crushing and refining,

         feeding, bean cleaning, sorting, milling and cream making

Hand decorating, inspection, wrapping and packing

150

200

300

Clay Products and Cements

Grinding, filter presses, kiln rooms moulding, pressing, cleaning  and  trimming

Enameling

Colour and glazing - rough work

Colour and glazing - fine work

150

150

400

750

        (Continued to next page)

Table 8.1.10  (Contd.)

Recommended Values of Illumination for Industrial Buildings and Processes

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(Ix)

Clothing Factories

Matching-up

Cutting, sewing

450

Light

Medium

Dark

300

450

700

Inspection

Light

Medium

Dark

450

1000

1500

Hand tailoring

Light

Medium

Dark

Pressing

450

1000

1500

300

Dairies

General working areas

Filling and bottle inspection

Cooling equipment

Laboratories

Pasteurizers 

Separators

200

450

150

450

150

150

Electrical Industries

Impregnating

250

Winding and insulating

500

Assembly works

Fine 

Very fine

500

750

Testing      

500

Electricity Generating Stations (Indoor Locations)

Turbine halls

Auxiliary equipment, battery rooms, blowers, auxiliary  generators,

switchgear and transformer chambers

Boiler house (including operating floors) platforms, coal conveyors,

pulverizers, feeders, precipitators,  soot and slag

  Boiler house and turbine house

Basements

Conveyor house, conveyor gantries and junction towers

150

100

70 to 100

100

70

70 to 100

Emergency lighting - all areas

30

 Control rooms

 Vertical control panels

 Control desks

 Rear of control panels

 Switch houses

200 to 300

300

150

150

Electricity Generating Stations (Outdoor Locations)

Switchyard

Conveyors 

Fuel oil delivery headers 

Oil storage tanks     

Cat-walks 

Platforms, boiler and turbine decks 

Transformer and outdoor switchgear

Emergency lighting - all areas

50

50

50

50

50

50

100

30

Flour Mills

Rolling  

Sifting 

Packing

Purifying

Product control

Cleaning screens, man lifts, aisleways and walkways, bin checking

150

150

150

150

300

100

        (Continued to next page)

Table 8.1.10  (Contd.)

Recommended Values of Illumination for Industrial Buildings and Processes

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(lx)

Forge Shops and Foundries

Forge shop

Annealing (furnaces) 

Cleaning 

Core making (fine) 

Core making (medium) 

Grinding and chipping 

Inspection (fine) 

Inspection (medium) 

Moulding (medium) 

Moulding (large) 

Pouring 

Sorting 

Cupola

Shake out 

150

150

100

300

150

200

1000

300

300

150

150

200

100

150

Garages

Parking areas (interior) 

Washing and polishing, greasing, general servicing and pits

70

150

Gas Works

Retort houses, oil gas plants, purifiers, coke screening and coke handling

plants (indoor)

Governor, meter, compressor, booster and exhauster houses

Open type plants

30 to 50

100

Cat-walks

Platforms

20

50

Glass Works

Furnace rooms, bending, annealing lehrs 

Mixing rooms, forming (blowing, drawing, pressing and rolling)

Cutting to size, grinding, polishing and toughening 

Finishing (bevelling, decorating, etching and  silvering)

Brilliant cutting

100

150

200

300

 General

 Fine

Inspection, etching and decorating

200

500

500

Glove Making

Pressing, knitting, sorting and cutting

Sewing

300

Light

Medium 

Dark

300

450

700

Inspection

Light

Medium 

Dark

450

1000

1500

Hosiery and Knitwear

Circular and flat knitting machines, universal winders, cutting out,  folding

       and pressing

Lock-stitch and overlocking machines

300

Light

Medium 

Dark

300

450

700

Mending 

Examining and hand finishing, light, medium and dark  

Linking or running on  

1500

700

450

        (Continued to next page)

Table 8.1.10  (Contd.)

Recommended Values of Illumination for Industrial Buildings and Processes

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(lx)

Iron and Steel Works

 Manufacturing by open hearth

Stock yard 

Charging floor  

Slag pits 

Control platforms

Mould yard

Hot top 

Hot top storage

Stripping yard

Scrap stockyard

Mixer building

Calcining building

20

100

100

100

25

100

100

100

20

100

50

Rolling mills

Blooming, slabbing, hot strip, hot sheet  

 Cold strip, plate

 Pipe, rod, tube, wire drawing

Merchant and sheared plate

100

150

200

100

Tin plate mills

Tinning and galvanizing 

 Cold strip rolling

Motor room, machine room

200

200

150

Sheet metal works

Miscellaneous machines, ordinary bench work 

Pressing, folding, stamping, shearing, punching and medium  bench work

200

200

Tin plate and galvanized sheet inspection

500

Structural Steel Fabrication

Fabrication and general work 

Marking and cutting 

150

300

Plating shops

Vat, baths, buffing and polishing  

Final  buffing and polishing

200

500

Leather Manufacturing

Cleaning, tanning and stretching, vats  

Cutting, fleshing and stuffing 

Finishing and scarfing

150

200

200

Machine shops

Rough bench and machine work 

Medium bench and machine work, ordinary automatic machines, rough grinding

medium buffing and polishing

Fine bench and machine work , fine automatic machines, medium grinding,  

fine buffing and polishing

Extra fine bench and machine work, grinding fine work

150

300

700

1000

Paint Works

General, automatic processes 

Special batch mixing 

Colour matching

200

450

700

Paper Manufacturing

Beaters, grinding, calendering  

Finishing, cutting, trimming, paper making machines  

Hand counting, wet end of paper machine  

Paper machine reel, paper inspection and laboratories 

Rewinder

Paper box manufacturing

150

200

350

500

500

200

        (Continued to next page)

Table 8.1.10  (Contd.)

Recommended Values of Illumination for Industrial Buildings and Processes

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(lx)

Pharmaceuticals and Fine Chemical Works

Raw material storage  

Grinding, granulating, mixing and drying,  tableting, sterilizing,

           preparation of solutions, filling, labelling, capping, wrapping and cartoning

Control laboratories and testing 

Fine chemical processing 

Fine chemical finishing

200

300

300

200

300

Printing Industries

Photo-engraving

Block-making, etching and staging 

Finishing, routing and proofing

200

300

 Masking and tint laying

300

Colour Printing

 Inspection area

700

Type foundries

Matrix making, dressing type  

Front assembly and sorting

Hand casting

Machine casting

250

200

300

200

Printing plants

Machine composition and imposing stones  

Presses  

Composition room  

Proof reading  

Colour inspection and appraisal

200

300

450

300

1000

Electrotyping

Block-making, electroplating, washing and baking 

Moulding, finishing and routing

200

300

Rubber Tyre and Tube Manufacturing

Stock preparation

Plasticating, milling  

Calendering

100

150

Fabric Preparation

Stock cutting, bead building  

Tube tubing machines  

Tread tubing machines  

250

250

250

 Tyre building

Solid tyre

Pneumatic tyre 

150

250

Curing department

Tubing curing, casing curing

350

Final Inspection

Tube, casing  

Wrapping

1000

200

Shoe Manufacturing (Leather)

Cutting and stitching

Cutting tables

Marking, buttonholing skiving, sorting and counting

450

450

Stitching

Light materials

300

Dark materials

1000

Making and finishing

Nailers, sole layers, welt beaters and scarfers, trimmers, welters,

lasters, edge setters, sluggers, randers, wheelers, treers, cleaning,

spraying,   buffing, polishing, embossing

600

        (Continued to next page)

Table 8.1.10  (Contd.)

Recommended Values of Illumination for Industrial Buildings and Processes

(for Occupancy classification see Chapter 2, Part 3)

Area or Activity

Illuminance

(lx)

Shoe Manufacturing (Rubber)

Washing, coating, mill run compounding  

Varnishing, vulcanizing, calendering, upper and sole cutting

Sole rolling, lining, making and finishing  process

100

300

500

Soap Factories

Kettle houses and ancillaries, glycerine evaporation  and distillation and continuous indoor soap making

General  areas

Control panels

150

200 to 300

Batch or continuous soap cooling, cutting and  drying, soap milling and plodding

General areas  

Control panels and key equipment

150

200 to 300

Soap stamping, wrapping and packing, granules  making, granules storage and

handling, filling and packing granules  

General areas

Control panels and machines

Edible products processing and packing

150

200 to 300

200

Textile Mills (Cotton)

Bale breaking and picking  

Carding  and drawing  

Slubbing, roving, spinning, spooling  

Beaming and slashing on comb

150

200

200

Grey goods 

Denims

200

300

Weaving

Patterned cloth and fine counts, light  

Patterned cloth and fine counts, dark  

Plain grey cloth  

Cloth inspection

300

500

200

700

Textile Mills (Silk and Synthetics)

Manufacturing

Soaking, fugitive tinting, conditioning, setting or twist

200

Winding, twisting, rewinding and coining, quilting and slashing

Light thread  

Dark thread

200

300

Warping (silk or cotton system) on creel, on running ends, on reel, on beam,

on warp at beaming  

300

Healding (drawing-in) 

Weaving

Inspection

700

300 - 500

1000

Textile Mills (Woollen and Worsted)

Scouring, carbonizing, testing, preparing, raising, brushing, pressing,

back-washing, gilling, crabbing  and blowing

Blending, carding, combing(white), tentering, drying  and cropping

Spinning, roving, winding, warping, combing (coloured)  and twisting

Healding (drawing-in) 

Weaving

150

200

450

700

Fine worsteds 

Medium worsteds and fine woollens  

Heavy woollens

700

450

300

Burling and mending

Perching

700

Grey

Final

700

2000

Wood Working

Rough sawing and bench work

Sizing, planing, rough sanding, medium machine and bench work glueing, veneering

Fine bench and machine work, fine sanding and finishing

150

200

300

Table 8.1.11

Recommended Values of Illumination for Storage Buildings

(for Occupancy classification see Chapter 2, Part 3)

                                     Area or Activity

Illuminance

(lx)

Storage Rooms of Ware House 

Inactive

Rough bulky

Medium

Fine

25

50

100

250

        1.4.1.1        Direct fittings shall  be used in situations where efficiency of illumination is the major criterion, while contract of the light source with the surroundings, shadows, and direct/reflected glare may be considered to be of relatively minor importance.

        1.4.1.2        Semidirect fittings shall be used in areas where it felt that the reduction of contrast resulting from the small indirect component of light directed towards the ceiling shall be sufficient for the purpose.

        1.4.1.3          General diffusing fittings shall be used where, in addition to a substantial indirect component of light aiding materially to the diffused character of the general illumination, an upward component providing a brighter background against which to view the luminance, especially for interiors with light-coloured ceiling and walls, is desirable.

        1.4.1.4          Semi-indirect fittings shall be used when a comfortable brightness ratio between the ceiling and the luminaire is desirable but an efficiency of illumination, higher than that obtainable from indirect fittings is required.

        1.4.1.5         Indirect fittings shall  be used in situations where an environment of evenly distributed illumination is to be achieved, efficiency of illumination not being a dominant factor.

1.5 ILLUMINATION OF EXIT SIGNS AND MEANS OF ESCAPE

1.5.1        Exit Signs

        1.5.1.1        All required exit signs shall be illuminated at night, or during dark periods within the area served.

        1.5.1.2        Exit signs  may be illuminated either by lamps external to the sign or by lamps contained within the sign. The source of illumination shall provide not less than 50 lux at the illuminated surface with a contrast of not less than 0.5. Approved self-luminous signs which provide evenly illuminated letters having a minimum luminance of 0.2 cd/m2 may also be used.

        1.5.1.3        Exit signs within an area where the normal lighting may be deliberately dimmed or extinguished, such as places of entertainment, shall be illuminated either by lamps contained within the sign or by approved self-luminous signs.

1.5.2        Means of Escape Lighting

        1.5.2.1        The means of escape and exit access in buildings requiring more than one exit shall be equipped with artificial lighting. The lighting facilities so installed shall provide the required level of illumination continuously during the period when the use of the building requires the exits to be available.

        1.5.2.2        The intensity of illumination at floor level in the means of escape shall not be less than 10 lux, except that the minimum required floor level illumination of aisles in assembly halls, theatres and cinema during projection of motion or still pictures by directed light shall be 2 lux.

        1.5.2.3        The illumination of exit signs and the lighting of the means of escape and exit access shall be powered by an alternate or emergency electrical system to ensure continued illumination for a duration of not less than 30 minutes after the failure of primary power supply.

Source: Bangladesh National Building Code 2006 (Housing and Building Research Institute). Superseded by BNBC 2020 — provided for reference. For design or official work, refer to the printed code.