Appendix A — Maximum Demand and Diversity
Gazette pages 4952–4954 · Official gazette pages (PDF, 100 KB) — use for exact tables and figures.
Some information on the determination of the maximum demand for an electrical installation is provided in this appendix. It also includes some notes on the application of allowances for diversity. It is impossible however, to specify the appropriate allowances for diversity for every type of installation since determination of such allowances calls for special knowledge and experience. The figures shown in Table 8.A.1 are therefore, intended to act as guideline. The current demand of a final circuit is determined by summing the current demands of all points of utilization and equipment in the circuit. Typical values to be used for this summation are given in Table 8.A.2. For blocks of residential dwellings, large hotels, and industrial and large commercial premises, allowances are to be assigned by a competent Engineer. The current demand of a circuit supplying a number of final circuits may be assessed by applying the allowances for diversity given in Table 8.A.2 to the total current demand of all the equipment supplied by that circuit. In the Table, the allowances are appraised either as percentages of the current demand or, where followed by the letters f.l., as percentages of the rated full load current of the current using equipment. After the design currents for all the circuits have been determined, enabling the conductor sizes to be chosen, it is necessary to check that the limitation on voltage drop is met.
Table 8.A.1: Allowances for Diversity
Purpose of final Type of Premises
circuit fed from Individual Small shops, stores, Small hotels,
conductors or household offices and business boarding houses,
switchgear to installations, premises guest houses, etc.
which diversity including dwellings
applies of a block
1. Lighting 66% of total current 90% of total current 75% of total current
demand demand demand
2. Cooking 10 amperes + 30% 100% f.l. of largest 100% f.l. of largest
appliances f.l. of connected appliance + 80% f.l. appliance + 80% f.l.
cooking appliances of 2nd largest of 2nd largest
in excess of 10 appliance + 60% f.l. appliance + 60% f.l.
amperes + 5 of remaining of remaining
amperes if socket appliances appliances
outlet is
incorporated in
unit.
Purpose of final Type of Premises
circuit fed from Individual Small shops, stores, Small hotels,
conductors or household offices and business boarding houses,
switchgear to installations, premises guest houses, etc.
which diversity including dwellings
applies of a block
3. Motors (other 100% f.l. of largest 100% f.l. of largest
than lift motors motor + 80% f.l. of motor + 50% f.l. of
______
which are 2nd largest motor + remaining motors.
subject to 60% f.l. of
special remaining motors
consideration)
4. Water heater
(thermostaticall No diversity allowable
y controlled)
Table 8.A.2: Current Demand to be Assumed for Points of Utilization and Current using Equipment
Point of Utilization or Current-using Current Demand to be Assumed
Equipment
15 A socket outlets 15 A with diversity applied
13 A socket outlets 13 A with diversity applied
5 A socket outlets At least 0.5 A
Protected outlets other than the above Rated current
mentioned socket outlets
Lighting outlet Current equivalent to the connected load,
with a minimum of 100 W per lamp
holder
House hold cooking appliance The first 10 A of the rated current plus
30% of the remainder of the rated current
plus 5 A if a socket outlet is incorporated
in the control unit
All other stationary equipment / Standard rated current or nominal current.
Appliances
Source: Bangladesh National Building Code 2020, S.R.O. No. 55-Law/2020, Bangladesh Gazette (Extraordinary), 11 February 2021. Tables, figures and equations: refer to the linked gazette pages.