Chapter 1 — General Provisions
Gazette pages 2860–2868 · Official gazette pages (PDF, 188 KB) — use for exact tables and figures.
Sections in this chapter
1.1 Scope
This Part of the Code prescribes regulations for safeguarding life and property in the use or occupancy of buildings or premises from the hazards of smoke and fire, and explosions. The provisions of this Part include general requirements of fire protection, precautionary requirements, means of egress, equipment and in-built facilities standard installations required for firefighting, and firefighting arrangements required for all occupancy groups.
1.2 Terminology
This Section provides an alphabetical list of the terms used in and applicable to this Part of the Code. In case of any conflict or contradiction between a definition given in this Section and that in Part 1, the meaning specified in this Part shall govern for interpretation of the provisions of this Part.
ALARM It consists of a circuit, controls, relays, switches and associated
CONTROL UNIT system which receive signals from alarm initiating devices and
transmit to alarm signaling devices.
ALARM An equipment operated manually or automatically which, when
INITIATING activated, initiates an alarm through an alarm signaling device.
DEVICE
ALARM SIGNAL Signals of audible or visual in nature, indicating the existence of
a fire and/or smoke condition. Audible devices may be bells,
horns, chimes, speakers or similar devices. Visual Alarms is a
strobe light emitting bright white light with approved insanity.
ALARM SIGNAL The equipment that produces the alarm signal.
DEVICE
ALARM SYSTEM It is a combination of compatible devices, which when activated
with necessary electrical energy can produce an alarm in the
event of fire.
ALARM ZONE It describes a defined area of the building or buildings for alarm
initiating locations.
ANNUNCIATOR Equipment capable of indicating the zone or area of a building
from which an alarm has been initiated or the location of such
devices and the operational condition of alarm circuit of the
system.
AUTOMATIC These include all types of fire detecting and alarm signaling
FIRE DETECTING devices which activate themselves during a fire without manual
AND ALARM intervention. The equipment/devices include temperature
SYSTEM sensitive fuses, thermostat, fluid filled tubes and electronic
devices which can detect a fire and transmit automatic alarm
signals.
AUTOMATIC The system consists of an array of pipe-works fitted with fusible
SPRINKLER solder or glass bulb. This system shall activate at a
SYSTEM predetermined temperature and the required water shall be fed to
the system from any source. In the event of fire or smoke the
system shall activate automatically by sensing the temperature
of fire and discharge water to extinguish. These devices also
actuate an audible alarm automatically.
AUTOMATIC This system applies water in the form of a conical spray
HIGH VELOCITY consisting of droplets of water discharged at high velocity
WATER SPRAY through specially designed projectors to extinguish fire by
SYSTEM emulsification, cooling and smothering.
BUILDING Any structure used or intended for supporting or sheltering any
use or occupancy.
BUILDING, A building erected or officially authorized prior to the effective
EXISTING date of the adoption of this edition of the Code by the agency of
jurisdiction.
CARBON This installation consists of a group of one or more cylinders of DIOXIDE carbon dioxide, interconnected by a manifold and feeding into a EXTINGUISHING system of high pressure distribution pipe work fitted with SYSTEM special discharge nozzles.
COMBUSTIBLE Any material which burns and enhances the magnitude of fire. MATERIAL
DRY-CHEMICAL This system consists of specially designed pipe works and
EXTINGUISHING discharge nozzles linked to the dry powder containers and
SYSTEM gaseous cylinders which are automatically/manually operated in
case of fire.
DRY RISER A riser or standpipe system is normally kept empty of water, but
is capable to discharge water within 45 seconds and its
installation is equivalent to wet-riser system.
ELEVATOR A system, including a vertical series of elevator lobbies and
EVACUATION associated elevator lobby doors, an elevator shaft(s), and a
SYSTEM machine room(s), that provides protection from fire effects for
elevator passengers, people waiting to use elevators, and
elevator equipment so that elevators can be used safely for
egress.
ELEVATOR A space from which people directly enter an elevator car(s) and
LOBBY to which people directly leave an elevator car(s).
EXTERIOR A stairway in which at least one side have openings more than
STAIRWAY 50% in an Exterior wall in such a way that there shall be no
accumulation of smoke during fire.
FIRE BARRIER A fire-resistance-rated wall inside a building, designed to
restrict the spread of smoke and fire. Opening in that wall, shall
be protected by fire protected doors or windows.
FIRE A space within a building that is enclosed by fire barriers on all
COMPARTMENT sides, including the top and the bottom to limit the transfer of
fire.
FIRE DAMPER A device installed in air ducts or air transfer openings or any
openings designed to close automatically upon detection of fire
or smoke.
FIRE DOOR See Fire door assembly.
FIRE DOOR Any combination of door leaf, frame, hardware and all other
ASSEMBLY accessories that together provide a specific degree of fire and
smoke protection to the opening where it is placed.
FIRE It expressed as a period of time and denotes the property of a
RESISTANCE building construction material or elements and/or construction
RATING as a whole during which the materials or elements or
constructions are (a) resistant to collapse due to fire, (b) resistant
to flame penetration and (c) resistant to excessive temperature
rise to the unexposed surface.
FIRE SEPARATION Refers to a fire-resistance-wall or slab between two buildings or two spaces to protect spread of smokes or fire vertically and horizontally.
FIRE TOWER Refers to a stairway open or enclosed, detached and isolated from any building by a distance and can be approached from various floors of a building or buildings by connecting passage only. FLOOR AREA, The floor area within the inside perimeter of the outside or GROSS exterior walls of the building under consideration with no deduction for hallways, stairs, closets, thickness of interior walls, columns, or other features. Gross floor area of a building means summation of gross floor areas of all the floors of a building. FLOOR AREA, The floor area within the inside perimeter of the outside or NET exterior walls of the building under consideration with deduction for hallways, stairs, closets, thickness of interior walls, columns, or other features or spaces not used for human occupancy. FOAM This system discharge foam to extinguish special fires. EXTINGUISHING SYSTEM HORIZONTAL Crossing a fire barrier of a building or connecting building in EXIT the same level shall be treated as horizontal exit. INTERIOR A designated area on ground or on water or on a portion of a STAIRWAY building for helicopter landing or takeoff without servicing, repairing and refueling facilities. INTERIOR A stairway within a building envelope. STAIRWAY PARTY WALL A fire resistance rated wall where openings are protected, which is constructed from the ground level and continued up to at least 1m above the roof of a building to restrict the spread of a fire. PUBLIC WAY A Street, alley, or other similar parcel of land essentially open to the outside air deeded, dedicated, or otherwise permanently appropriated for building users or for public use or a single loaded corridor that is one lateral side opened to outer air, designed in such a way that there shall be no accumulation of smoke in case of fire. This corridor may be placed at any level of a building having a clear width and height of not less than 3 meter having guards and connected to the exit termination or refuge areas by exterior or enclosed stairs shall be treated as public way.
ROOF REFUGE When occupants are relocated at the flat roof of a building
AREA which are not connected with any means of exit shall be treated
as isolated refuge area and must have provisions for placing of
leaders of fire department excess vehicles.
SMOKE A devise capable of sensing visible or invisible particles DETECTOR produced during combustion.
TRAVEL Straight line distance between the remotest point of a space of a DISTANCE floor and the exit access door placed thereof.
TRAVEL PATH Length of a passage from the remotest point of a space up to the exit access door placed thereof.
VENTILATION Natural or mechanical intake of fresh air from outside and removal of inside air of an enclosed space.
VESTIBULE A compartment provided with two or more doors with smoke lock system where the intended purpose is to prevent continuous and unobstructed passage by allowing the release of only one door at a time.
VENT, FIRE A system which activates itself automatically or manually during a fire or can be activated manually to release the heat and smoke generated by the fire and smoke.
RAMP A walking surface that has a slope steeper than 1 in 20 and accessible ramps are not steeper than 1 in 12.
WET-CHEMICAL A system where a solution of water and potassium carbonate EXTINGUISHING and/or potassium acetate based chemical forms the SYSTEM extinguishing agent.
WET RISER A vertical pipe or consists of an array of pipes installed
STAND PIPE vertically in a building having landing valves with appropriate
SYSTEM outlets at various levels of a building containing charged water
at a specified pressure for fire extinguishing purposes.
1.3 General Requirements
The provisions of this Section shall specify the general requirements in respect of height and area limitations, open space requirements and access facilities for the fire service, which are to be provided for a building to protect it from potential fire hazards.
1.3.1 Height and Area Limitations
The height and area limitations of all buildings and structures shall be governed by the occupancy group classification, floor area ratio and type of construction, which are specified in Part 3 of this Code.
1.3.2 Open Space or Fire Separation Requirement
For the purpose of applying the provisions of open space or fire separation requirements of a building at its side, rear and frontages in Part 3 of this Code shall be followed.
1.3.3 Access Facilities for Fire Service
The access facilities for fire service vehicles and engines shall meet provisions provided in Part 3 of this Code.
1.4 Fire Drill
Fire drills based on fire order shall be arranged to train the occupants of a building in first-aid firefighting, relocation and orderly evacuation. The occupants shall be made thoroughly conversant with fire order, firefighting, and relocation and evacuation procedures in the event of an emergency. The guidelines of fire drill, relocation and evacuation procedure are given in Appendix A.
1.5 Fire Tests and Fire Resistance Rating
The fire resistance rating of individual building construction components shall be
determined by standard materials testing procedure as detailed below.
(a) The fire resistance ratings of building assemblies and structural elements
shall be determined in accordance with ASCE 29 or ASTM E 119.
(b) The construction materials which are intended to be classified as non-
combustible shall be tested in accordance with ASTM E 136.
(c) Flame resistance rating of all materials used for interior finish and trim shall
be tested in accordance with ASTM E 84.
(d) The fire door assemblies shall conform to the test requirements of ASTM
E 152.
(e) The fire windows and fire shutters shall meet the test requirements of ASTM E 163.
(f) The fire resistances rating of structural elements are provided in Table 4.1.1. For details refer to ASCE 29.
Table 4.1.1: Fire Resistance of Structures
Concrete Minimum Equivalent Thickness of Concrete Walls, Floors, and
Aggregate Roofs for Fire Resistance Rating
Type 1 hr 1.5 hr 2 hr 3 hr 4 hr
in mm in mm in mm in mm In mm
Siliceous 3.5 89 4.3 109 5.0 127 6.2 157 7.0 178
Carbonate 3.2 81 4.0 102 4.6 117 5.7 145 6.6 168
Sand-light 2.7 69 3.3 84 3.8 97 4.6 117 5.4 137
weight
Lightweight 2.5 64 3.1 79 3.6 91 4.4 112 5.1 130
Concrete Minimum Column Dimension for Fire Resistance Rating
Aggregate 1 hr 1.5 hr 2 hr 3 hr 4 hr
Type
In mm in mm in mm in mm in mm
Siliceous 8 203 9 229 10 254 12 305 14 356
Carbonate 8 203 9 229 10 254 11 279 12 305
Sand-light 8 203 8.5 216 9 229 10.5 267 12 305
weight
Clay Minimum Required Equivalent Thickness of Masonry for Fire
Masonry Resistance Rating
Unit 0.5 hr 0.75 hr 1 hr 1.5 hr 2 hr 3 hr 4 hr
in mm in mm in mm in mm in mm in mm in mm
Brick of clay or 1.7 43 2.0 51 2.3 58 2.85 72 3.4 86 4.3 109 5.0 127
shale, unfilled
Brick of clay or 2.3 58 2.65 67 3.0 76 3.7 94 4.4 112 5.5 140 6.6 168
shale, grouted
or filled with
perlite,
vermiculite, or
expanded shale
aggregate
1.6 Related Appendix
Appendix A Fire Drill and Evacuation Procedure
Source: Bangladesh National Building Code 2020, S.R.O. No. 55-Law/2020, Bangladesh Gazette (Extraordinary), 11 February 2021. Tables, figures and equations: refer to the linked gazette pages.