Appendix K — Sound Absorption Coefficients Table 8.K.1: Sound Absorption Coefficients a
Gazette pages 4973–4976 · Official gazette pages (PDF, 188 KB) — use for exact tables and figures.
Source: Stein, B. et al., 2006. Mechanical and Electrical Equipment for Buildings. John Wiley & Sons, New Jersey Absorption Coefficients (α) 500 1000 2000 4000 NRCc 125 Hz250 Hz General Building Materials and Furnishings b Hz Hz Hz Hz
Brick, unglazed 0.03 0.03 0.03 0.04 0.05 0.07 0.005
5
Brick, unglazed, painted 0.01 0.01 0.02 0.02 0.02 0.03 0.00
Carpet, heavy, on concrete 0.02 0.06 0.14 0.37 0.60 0.65 0.29
Carpet, heavy, on 1.36 kg/m2 hair felt or foam rubber 0.08 0.24 0.57 0.69 0.71 0.73 0.55
Concrete block, coarse 0.36 0.44 0.31 0.29 0.39 0.25 0.35
Concrete block, painted 0.10 0.05 0.06 0.07 0.09 0.08 0.05
Fabrics
Light velour, 0.34 kg/m2, hung straight, in contact with 0.03 0.04 0.015 0.17 0.24 0.35 0.15 wall Medium velour, 0.47 kg/m2, draped to half area 0.07 0.31 0.49 0.75 0.70 0.60 0.55
Heavy velour, 0.61 kg/m2, draped to half area 0.14 0.35 0.55 0.72 0.70 0.65 0.60
Floors
Concrete or terrazzo 0.01 0.01 0.015 0.02 0.02 0.02 0.00
Linoleum, asphalt, rubber, or cork tile on concrete 0.02 0.03 0.03 0.03 0.03 0.02 0.05
Wood 0.15 0.11 0.10 0.07 0.06 0.07 0.10
Glass
Large panes of heavy plate glass 0.18 0.06 0.04 0.03 0.02 0.02 0.05
Ordinary window glass 0.35 0.25 0.18 0.12 0.07 0.04 0.15
Gypsum board, 13 mm nailed to 50x100 mm stud 400 0.10 0.08 0.05 0.03 0.03 0.03 0.05 mm c/c Marble or glazed tile 0.01 0.01 0.01 0.01 0.02 0.02 0.00
Openings Stage, depending on furnishings 0.25-0.75 Deep balcony, upholstered seats 0.50-1.00 Grillese ventilating 0.15-0.50
Absorption Coefficients (α)
General Building Materials and Furnishings b 125 250 500 1000 2000 4000 NRCc
Hz Hz Hz Hz Hz Hz
Plaster, gypsum or lime, smooth finish on tile or brick 0.013 0.015 0.02 0.03 0.04 0.05 0.05
Plaster, gypsum or lime, on lath 0.14 0.10 0.06 0.05 0.04 0.03 0.05
Plywood panelling, 9 mm thick 0.28 0.22 0.17 0.09 0.10 0.11 0.15 Rough wood, as tongue-and-groove cedar 0.24 0.19 0.14 0.08 0.13 0.10 0.14 Slightly vibrating surface (e.g., hollow core door) 0.02 0.02 0.03 0.03 0.04 0.05 0.03 Readily vibrating surface (e.g., thin wood panelling on 0.10 0.07 0.05 0.04 0.04 0.05 0.05 400 mm studs) Water surface, as in swimming pool 0.008 0.008 0.013 0.015 0.020 0.025 0.00
Absorption of Seats and Audience d 125 250 500 1000 2000 4000 NRCc
Hz Hz Hz Hz Hz Hz
Audience, in upholstered seats, per 0.093 m2 of floor 0.60 0.74 0.88 0.96 0.93 0.85 -
area
Unoccupied cloth-upholstered seats, per 0.093 m2 of 0.49 0.66 0.80 0.88 0.82 0.70 -
floor area
Wooden pews, occupied, per 0.093 m2 of floor area 0.57 0.61 0.75 0.86 0.91 0.86 -
Students in tablet-arm chairs, per 0.093 m2 of floor 0.30 0.42 0.50 0.85 0.85 0.84 -
area
125 250 500 1000 2000 4000
Acoustic Absorptive Materials Mtge Hz Hz Hz Hz Hz Hz NRC
c
High-performance vinyl-faced fibreglass Ceiling panels 25 mm thick E405 0.73 0.88 0.71 0.98 0.96 0.77 0.90 38 mm thick E405 0.79 0.98 0.83 1.03 0.98 0.80 0.95 Painted nubby glass cloth panels 6 mm thick E405 0.81 0.94 0.65 0.87 1.00 0.96 0.85 25 mm thick E405 0.78 0.92 0.79 1.00 1.03 1.10 0.95
Random fissured 19 mm-thick panels E405 0.52 0.58 0.60 0.80 0.92 0.80 0.70 Perforated metal panel with infill 1 in. thick E405 0.70 0.86 0.74 0.88 0.95 0.86 0.85 Typical averages, mineral fibre tiles and panels
19 mm fissured E405 0.47 0.50 0.52 0.76 0.86 0.81 0.65
19 mm textured E405 0.49 0.55 0.53 0.80 0.94 0.83 0.70 16 mm fissured E405 0.28 0.33 0.66 0.73 0.74 0.75 0.60
16 mm textured E405 0.29 0.35 0.66 0.63 0.44 0.34 0.50
16 mm perforated E405 0.27 0.29 0.55 0.78 0.69 0.53 0.60
75 mm in thick x 400 mm square on 600 mm A 0.40 0.61 1.92 2.54 2.62 2.60 centres
a This table primarily useful for preliminary calculations. Complete tables of coefficients may be found in books on architectural acoustics. b Selected data courtesy of Owens-Corning Fibreglass. c NRC: the arithmetic average of the α values at 250, 500, 1000, and 2000 Hz. d If audience is randomly spaced, use an average or 0.47 m2 sabins per person. e See figure at right for mounting methods Type A and Type E 405.
Source: Bangladesh National Building Code 2020, S.R.O. No. 55-Law/2020, Bangladesh Gazette (Extraordinary), 11 February 2021. Tables, figures and equations: refer to the linked gazette pages.